The following is a list of basic fire door requirements. This list may not encompass all requirements so make sure to check your local building codes.

1. The unit must be self-closing. 2. The unit must be self-latching. 3. The unit must have a Label attached. 4. The Door Frame must have an attached or embossed Label.

9. The maximum glass allowed in a 60- or 90-minute rated door is a 100 sq. in. per lite. 10. A Fire Door with a Louver requires a Fusible Link Louver. 11. No Louvers are allowed in fire-rated doors with lite kits. 12. No Louvers are allowed in doors with Panic Exit Hardware or Stairwells. 13. The maximum Fire-Rated louver size is 24″ x 24″.

5. The unit must have Steel Bearing Hinges. 6. The unit must have “Listed” Hardware.

7. If a Fire Door is held open, it must have a “UL-Listed”, heat fusible link or smoke detection device (or be tied into the fire alarm system). 8. A maximum of 1296 square inches of visible glass is allowed to achieve a 20 or 45 minute rating.